Fire retardant frame systems for direct flush TEMPOFIX 3 with TEMPOFLUX 3 /


            The French by-law from 25 June 1980 specifies rules of safety against the risk of fires and panic in public and commercial buildings.
            Buildings with accommodation like hotels, care homes and hospitals are particularly concerned.

            If drilling > 75mm in a fire retardant partition (e.g. for a pipe), the building must have an adequate device to prevent the spread
            of fire to other areas.


            "§ 3. Pipes with a diameter larger than 75 millimetres and less than or equal to 315 millimetres must be flame retardant
            for 30 minutes for the walls in public and commercial buildings with the exception of horizontal pipes which can be fire resistant
            for 15 minutes."
            Extract from Article CO 31 in the French by-law from 25 June 1980 approving general safety rules against the risk of fires and panic
            in public and commercial buildings, modified by 26 June 2008 by-law.



            With DELABIE's fire retardant solution, the installation of the TEMPOFIX 3 guarantees:
              •  A space saving solution which is practical and looks good whilst being fire retardant for 60 minutes.
              •  Easy maintenance from the front (behind the control plate) without the need for access to a service duct.
              •  Suitable for walls 53 to 105mm.

            Fire retardant solution CF 60 min - EI60 complies with fire safety regulations for public and commercial buildings.
            (Tests carried out by Firelab laboratories certified by the COFRAC and meeting ISO 834 standard).


            In the UK Regulatory Reform (Fire Safety) Order 2005 sets out the guidelines for keeping premises safe and preventing fires.


















                                                                                                                          CISTERN-LESS WCs


























            Two TEMPOFIX 3 fire retardant frame systems installed back to back.