PREMIX SECURITY Group thermostatic mixing valve
Ref. 731054
For circulating loops 44°-58°C
For circulating loops 44°-58°C
DESCRIPTION
PREMIX SECURITY Group thermostatic mixing valve
Ref. 731054Group thermostatic mixing valve for hot water circulating loops adjustable from 44°C to 58°C:
Anti-scalding safety.
Regulates temperature variations.
Non-return valves and filters accessible from the exterior without having to remove the mechanism.
Thermal shocks are possible.
Interchangeable cartridge with thermo-reactive cell.
High-resistance chrome-plated brass body.
Maximum hot water temperature: 85°C.
Differential hot water / mixed water: 15°C minimum.
Pressure differences at the inlets: 1 bar maximum (0.5 bar recommended).
Minimum pressure / maximum: 1 to 10 bar (1 to 5 bar recommended).
Left hand side hot water inlet (red ring) and right hand side cold water inlet (blue ring).
Mixed water outlet at the top (purple ring) for bottom outlet: unscrew / place lid at the top and outlet connector at the bottom.
Safety and prolongation of system life span (Hot water > 65°C leads to premature aging within the system).
Maximum temperature limiter, can be adjusted by the installer.
Reduced risk of scalding by limiting temperature at the point-of-use.
140 lpm - M1¼".
30-year warranty.
Anti-scalding safety.
Regulates temperature variations.
Non-return valves and filters accessible from the exterior without having to remove the mechanism.
Thermal shocks are possible.
Interchangeable cartridge with thermo-reactive cell.
High-resistance chrome-plated brass body.
Maximum hot water temperature: 85°C.
Differential hot water / mixed water: 15°C minimum.
Pressure differences at the inlets: 1 bar maximum (0.5 bar recommended).
Minimum pressure / maximum: 1 to 10 bar (1 to 5 bar recommended).
Left hand side hot water inlet (red ring) and right hand side cold water inlet (blue ring).
Mixed water outlet at the top (purple ring) for bottom outlet: unscrew / place lid at the top and outlet connector at the bottom.
Safety and prolongation of system life span (Hot water > 65°C leads to premature aging within the system).
Maximum temperature limiter, can be adjusted by the installer.
Reduced risk of scalding by limiting temperature at the point-of-use.
140 lpm - M1¼".
30-year warranty.
ADVANTAGES

Automatic shut-off if cold water supply fails

Temperature stability

Accessible filters and non-return valves

Thermo-reactive cell
TECHNICAL CHARACTERISTICS
PREMIX SECURITY Group thermostatic mixing valve
Ref. 731054Connector | M1"1/4 |
Technology | Thermostatic |
Height | 90mm |
Depth | 26mm |
Length | 180mm |
Flow rate | 140 lpm |
Certificates |
![]() ![]() ![]() |
Warranty | ![]() |
VARIANTS
731052 | 55 lpm - M3/4" - Dimensions: 120 x 60 x 18mm | ||
---|---|---|---|
731053 | 90 lpm - M1" - Dimensions: 160 x 80 x 23mm | ||
731055 | 190 lpm - M1 1/2" - Dimensions: 195 x 98 x 26mm |
VARIANTS
731052 | 55 lpm - M3/4" - Dimensions: 120 x 60 x 18mm | ||
---|---|---|---|
731053 | 90 lpm - M1" - Dimensions: 160 x 80 x 23mm | ||
731055 | 190 lpm - M1 1/2" - Dimensions: 195 x 98 x 26mm |